FC300
Chapter 1 Summarize
Rated
current A
7.5
11
16
22
27
36
49
73
96 111
Input Voltage V
single phase 220V±15%
Frequency
HZ
50/ 60Hz
Rated
current A
5.0 7.0 11
15
18
25
33
49
65
75
Voltage V
three phase 0-220V
Output
Frequency
HZ
Overload
protection
0-1000Hz
200% 0.1S
150% 60S
Notes:
1. Maximum adapted motor means the maximum power light load engine for the drive of the
certain inverter model, by the standard of four-pole motor.
2. Rated output current means the output current when output voltage is 380V (or 220V).
3. Overload capacity is represented by the percentage of the overcurrent to the rated current.
When using it repeatedly, please wait till the temperature of inverter and motor decrease
below the temperature under 100% load.
4. Maximum output voltage CANNOT exceed power supply voltage. Below power supply
voltage, any output voltage can be set freely(voltage peak value of inverter output terminal
is DC voltage).
5. Power supply capacity changes according to the value of impedance (including input
reactor and cable ) on the side of power supply.
1.4 Braking Unit and Braking Resistor
Inverter
Voltage
Power KW
0.75
1.5
Single phase
220V
2.2
3.0
3.7
0.55
Three-phase
380V
0.75
1.5
Braking unit
Configura Quanti
-tion
-ty
preset
1
preset
1
preset
1
preset
1
preset
1
preset
1
preset
1
preset
1
Braking resistor
Configuration
Specification
externally mounted 100W /150Ω
externally mounted 400W/100Ω
externally mounted 600W/100Ω
externally mounted 800W/100Ω
externally mounted 800W/100Ω
externally mounted 100W /750Ω
externally mounted 100W /750Ω
externally mounted 260W/400Ω
Quantity
1
1
1
1
1
1
1
1
5
    "