Chapter 6 RS485 Communication protocol
Read 1# inverter status inverter respondsas forward running
Request: 0x01 0x03 0x81 0x000x00 0x010xac 0x36
Response: 0x01 0x03 0x020x01 0xa00xb9 0xac
Remark: 0x8100: inverter status words
0x0001: read a word
0x02: return two bytes
0x01a0: BIT5=1 inverter forward run
no fault
6.8 Communication Network Formation
The connection of one inverter to computer
FC300
The connection of several inverters connected to computer
NoticeOnly the furthest inverter requires to be connected to termination resistor(240 Ω).