FC300
Chapter 4 Detailed Parameter Description
P117
P118
P119
P120
P121
P122
P123
P124
P1125
P126
P127
P128
P129
Proportionality
factor
Integration
factor
Differential
factor
Feedback
sampling cycle
PID relative
parameters
PID target value
Reserved
Reserved
Reserved
Present count
value
Count preset
Count & warn
Count arrival
choice
Setting range: 0.01—10.00
When this factor value is big it gives a quick response,
but if it is too big it may cause oscillation. When this
factor value is small, it gives a slow response.
Setting factor: 0.01—10.00
When this factor value is big it gives a quick response.
Setting range: 0.01—10.00
When this factor value is big it gives a quick response,
but if it’s too big it may cause oscillation. When this
factor value is small, it gives a slow response.
Setting range : 0.1—20.0S
This factor sets the interval time for next response
under PID controller.
This parameter consists four hexadecimal digits D3,
D2, D1, D0, each of which represents a different
function.
D0, Decimal place setting of PID displayed value :
Setting range: 0-3
D1, Relation between motor speed and feedback
0, when motor rotating speed rises, feedback value
increases;
1, when motor rotating speed rises, feedback value
decreases.
Setting range: PID minimum target value-PID
maximum target value.
Automatic memory when power-off.
Setting value: 0—65000
This parameter sets the present count value of
counter. External counting pulse signal makes this
parameter increase.
Setting : 0—65000
This function is to set the preset value of counter.
When count value equals to count preset value,
system acts according to P129.
Setting range: 1—65000
This function is for setting a warning value of counter,
to prepare for next work procedure before count
arrival. When count reaches warning value, system
outputs signal through terminal.
Setting range:
0, shut off output;
1.00
0.50
0.50
0.3
0x0002
5000
0
100
90
0
33
    "