Chapter 4 Detailed Parameter Description
FC300
P108
P109
P110
P111
P112
P113
P114
P115
P116
32
Corresponding
analog output of
highest
frequency (PID
biggest target
value)
Corresponding
analog output of
lowest
frequency (PID
smallest target
value)
Reserved
Reserved
Running mode
PID maximum
target value
PID minimum
target value
Corresponding
feedback to PID
maximum target
value
Corresponding
feedback to PID
minimum target
value
Setting range: 0—100%
It is to set the corresponding relation between analog
and target frequency (PID target value).
E.g. When AVI terminal inputs 10Vx98%=9.8V,
frequency reaches highest frequency (P021)
Setting range: 0—100%
It is to set the corresponding relation between analog
and target frequency (PID target value).
E.g. When AVI terminal inputs 10V x 2%=0.2V,
frequency reaches lowest frequency (P022)
Setting range:
0, Common running
1, PID mode, target value is set by operation panel, AVI
terminal inputs feedback;
2, PID mode, target value is set by operation panel, ACI
terminal inputs feedback;
3, Target value is set by AVI terminal, ACI terminal
inputs feedback.;
4, Target value is set by ACI terminal, AVI terminal
inputs feedback;
5-9, Reserved;
10, Program runs, then stops after one single circle;
11, Program runs, then runs at the latest speed after
one single circle;
12, Program runs, then runs in round trip..
This parameter is to choose the running mode of
inverter.
Setting range: minimum target value-10000
This function is to set the maximum target value
during PID running. The decimal point position on
operation panel can be set on P121.
Setting range: 0-maximum target value.
This function is to set the minimum target value during
PID running.
Setting range: 0—100%
It is to set the corresponding sensor feedback to
maximum target value.
Setting range: 0—100%
It is to set the corresponding sensor feedback to
minimum target value.
98
2
0
10000
0
100
0
    "