CW-5000/5200 Series
7. Advanced parameters adjustment case:
Order Code
1
F0
2
F1
3
F2
4
F3
5
F4
6
F5
7
F6
8
F7
9
F8
10
F9
Item
Temperature
setting
Temperature
Difference values
Cooling
hysteresis
Way of control
Alarm for over high
water temperature
Alarm for over low
water temperature
Alarm for over high
Room temperature
Password
The allowed highest
water temperature
The allowed lowest
water temperature
Value in
case 1
Value in
case 2
28
Value in
case 3
25
T-503
Temperature
controller
Factory Setting
T-504
Temperature
controller
Factory Setting
25
25
-3
-2
-2
0.5
2.0
1.0
0.8
0.1
1
0
0
1
0
10
5
4
10
10
10
10
14
15
15
45
45
45
45
45
8
8
8
8
8
31
30
30
30
30
25
5
5
20
20
(1) Case 1: cooling water temperature is controlled by intelligent mode. Requiring
water temperature to be between 25ć to 31ć. Ambient temperature keeping
constant, when the set water temperature is 3ć lower than the ambient, the
fluctuation will not exceed f 0.5 ć . There will be an alert when water
temperature is 10 ć lower or higher than target. (e.g. when ambient
temperature is 30.0ć, cooling water temperature is between 27.5ć to 26.5ć,
if ambient temperature is up to 30.5ć, water temperature will be between 28.0
ć to 27.0ć.)
(2) Case 2: cooling water temperature is controlled by constant mode. Requiring
water temperature is constant in 28ć, and the fluctuate does not exceed f2ć.
The alarm of over high water temperature will be on when water temperature is
5ć higher than normal, and the alarm of over low water temperature will be on
when water temperature is 10ć lower than normal.
(3) Case 3: cooling water temperature is controlled by constant mode. Requiring
water temperature is constant in 25ć, and the fluctuate does not exceed f1ć.
The over high water temperature will be on then water temperature is higher
than 30ć, and the alarm of over low water temperature will be on when water
temperature is lower than 10ć. (No matter what is the ambient temperature,
the cooling water temperature is constant in 24.0ć to 26.0ć)
9