CHAPTER 13 RS-485 COMMUNICATIONS
13
13.1.2 Communication Specifications
Item
Electric I/F
Communication
speed
Specifications
RS-485
38400192009600115200 bps
Remarks (PA is a parameter No.)
Set by parameter PA2_73
Synchronization
method
Asynchronous (UART)
Communication
Semi-duplex communication
method
Transmission format
Connection cable
Master-slave (servo amplifier) = 1:N
(1N31)
LAN cable (straight) or equivalent
Max. 31 units connected
simultaneously
Cable length
(recommneded)
Entire extended length:
100 m or less (up to 38400 bps)
40 m or less (115200 bps)
Length between stations:
20 m or less
Terminator treatment Master side
Slave side
:100
recommended
: Unnecessary
Character
configuration
Start bit
Data length
Parity
Stop bit
: 1 bit
: 8 bits
: Even/Odd/None
: 1 or 2 bits
Set by parameter PA2_93
Communications
protocol
Compliant with Modbus RTU protocol
Communications
mode
RTU mode
The ASCII mode is not
supported.
Station number
0: Broadcast
1-31: Slave station No.
Set by parameter PA2_72
Function code (FC)
1(01h): Read out coil data
3(03h): Read out various data
5(05h): Write in single coil data
8(08h): Maintenance (echo back)
15(0Fh): Write in coil data
16(10h): Write in various data
23(17h): Read out/write in various data
Responses other than those in
the left cell are exceptional
responses (improper FC).
Error check method CRC-16 method
Message length
Variable length
Max. 200 bytes
Frame
synchronization
method
Timing synchronization
Frames are initialized if time
data for three characters are
absent.
It is recommended to use the RS-232C - RS-422 converter (model: NW0H-CNV) for the use of 1:1
communications between the master and the slave (servo amplifier). Do not use it for multiple unit
connection.
13-4 Modbus RTU Communications