CHAPTER 12 POSITIONING DATA
12
12.1.2 Operation Mode Selection
Positioning operation based on positioning data and immediate value data can be conducted with this
servo amplifier.
To change the operation mode, enter parameters shown in the table below and supply an input signal.
The setting in operation mode (1) is enabled if “77” (positioning data selection) is not specified with the
CONT signal.
<Operation mode (1)>
Control mode
selection:
PA1_01
Internal
positioning
data
selection:
PA2_40
7: Positioning 1: Enable
operation
Sequential
start
selection:
PA2_41
0: Disable
1: Enable
2: Homing
3: Immediate
value data
operation
AD3
OFF
OFF
AD2 AD1
OFF OFF
OFF OFF
~
AD0
Operation
OFF
Address error
Sequential start
Homing
Immediate value
data operation
ON Operation with
positioning data
No. 1
~
ON
ON
ON
ON
0: Disable
PA2_97: Communication protocol selection = 1 *
Immediate value data operation is impossible with the PC Loader protocol.
Operation with
positioning data
No. 15
Operation with
immediate value
data
12-4 Operation Modes