CHAPTER 7 MAINTENANCE AND INSPECTION
7
The position shifts from an
intended one in pulse operation.
Check the pulses of PLC output and amplifier
command integration.
PLC output pulse≠command
integration pulse
PLC output pulse = command integration pulse
Check the travel amount per pulse.
Abnormal
Not abnormal
There is a mechanical abnormality.
Abnormal
Not abnormal
Contact us.
(1) Check the wiring for pulses.
(2) Check noise occurrence.
(3) Check PA1_03 (command pulse form
selection).
Check the setting of electronic gear.
(1) Check the machine for overload or
mechanical slip, etc.
The motor does not operate in a
smooth manner (operates
choppily).
Check PA1_14 (load inertia ratio).
Moment ratio<50
Check the acceleration/deceleration torque.
Not abnormal
There is a mechanical abnormality.
Not abnormal
IMneormtiaenrtartaiotio≥≧5050
300M%aox.r 3m0o0r%e torque is required.
Abnormal
Contact us.
Select "1" (semi auto) in PA1_13 (tuning
mode selection) and set the PA1_14
parameter appropriately.
Extend the acceleration/deceleration time.
(Reference: The acceleration/deceleration
torque becomes 250% or less.)
Check the machine for backlash or
mechanical slip, etc.
7-22 Troubleshooting