CHAPTER 7 MAINTENANCE AND INSPECTION
The servo motor has operated
briefly and stopped.
Check if an alarm is raised or not.
No alarm is raised.
Check if the brake is released.
The brake is released.
There is a mechanical abnormality.
Not abnormal
Contact us.
An alarm is raised.
Check the cause by referring to section 7.3.
The brake is not released.
(1) Check the brake power.
(2) Check the brake ON/OFF sequence.
Abnormal
(1) Check the machine for the stroke end or
mechanical slip, etc.
The motor issues unpleasant
noise.
Check if the motor is oscillating or not.
Not oscillating
Check if the brake is released.
The brake is released.
Check the wiring of power to the servomotor.
Not abnormal
Check the wiring of the encoder cables.
Not abnormal
There is a mechanical abnormality.
Not abnormal
Contact us.
Oscillating
Reduce the PA1_15 (auto tuning gain 1)
value.
The brake is not released.
(1) Check the brake power.
(2) Check the brake ON/OFF sequence.
Abnormal
Abnormal
Abnormal
(1) Check the wiring of U/V/W.
(2) Check if the wiring is connected to a
wrong motor or not.
(1) Check the encoder cables.
(2) Check if the wiring is connected to a
wrong motor or not.
(1) Check the machine for the stroke end or
mechanical slip, etc.
7
Troubleshooting 7-21