CHAPTER 7 MAINTENANCE AND INSPECTION
7.7 Troubleshooting
The servomotor does not operate.
7
Check the connections and contact statuses of the * Before checking the connections of cables and connectors, make sure to turn off
cables or connectors for power supply and others. the power.
Check On01 (feedback speed).
Check Sn01.
* This is necessary because if deceleration feature has been applied or the motor is
operated in extremely low speed, the motor operation status cannot be checked by
visual check. Furthermore, there is a possibility of mechanical slip.
Abnormal (The motor is not in operable
condition.)
Check the cause by referring to section 6.3.
Not abnormal
Check if an alarm is raised or not.
An alarm is raised.
Check the cause by referring to section 7.3.
No alarm is raised.
Check if any command such as FWD/REV, pulse,
analog voltage, or START, etc. has been input.
Abnormal (No such command has been
inp ut.)
Check the sequence of the host controller.
Check the diagnosis of the PC loader.
Not abnormal
Check the relevant parameters.
Not abnormal
(1) In the case of pulse operation
PA1_01 (control mode selection)
PA1_03 (command pulse input method
and form setting)
(2) In the case of multi-step speed selection
operation
PA1_41 to 47 (manual feed speed )
PA3_1 to 30 (CONT signal assignment)
(3) In the case of analog command
PA3_31 (speed command scale)
PA3_35 (zero clamp level)
(4) In the case of start positioning
PA1_01 (control mode selection)
PA2_40 (internal positioning data selection)
Internal positioning data
(5) In the case of Modbus communications
PA2_97 (communication protocol selection)
PA2_72 (station number)
Contact us.
7-20 Troubleshooting