CHAPTER 7 MAINTENANCE AND INSPECTION
3. Overvoltage
[Display]
Hu
[Description of detected alarm]
The DC voltage inside the servo amplifier exceeds the upper limit.
[Cause and remedy]
Cause
Remedy
The source voltage is too high
(immediately after power-on).
Check if the source voltage is within the specification
limits.
Insert a reactor if there is a power factor improvement
capacitor.
Unconnected external regenerative Connect the external regenerative resistor.
resistor or wrong wiring
Correct the wiring of the external regenerative resistor.
Broken regenerative transistor
Replace the servo amplifier.
The internal DC voltage can be checked in the monitor mode of the keypad.
[on15]: Internal DC link voltage (max. value)
Approximately over 420 V, overvoltage is detected.
4. Encoder Trouble
[Display]
[Description of detected alarm]
7
Et1
Et2
There is a fault in the encoder built in the servomotor.
(Communications are normal.)
Et1: Single revolution position detection fault of encoder
Et2: Encoder memory data reading fault
[Cause and remedy]
Cause
Fault in data sent from encoder
Failure of encoder
Remedy
Use shielded cables to eliminate noise effects.
Replace the servomotor.
5. Circuit Trouble
[Display]
ct
[Description of detected alarm]
There is a fault in the source control power voltage inside the
servo amplifier. There may be a failure in the internal circuit.
[Cause and remedy]
Cause
Failure of servo amplifier
Remedy
Turn the power off then on again. If restoration
is not obtained, replace the servo amplifier.
Troubleshooting Method 7-7