CHAPTER 4 PARAMETER
(4) Upon detection of the first encoder Z-phase (PA2_11) after detection of the home position LS
(PA2_12) during travel in the homing direction after reference signal detection (PA2_10), a
travel continues by the home position shift unit amount (PA2_14), followed by stoppage. The
stopping point changes to the home position and homing completion is turned on and the
homing process is finished.
Home position shift unit amount
Encoder Z-phase
(3)
(4)
(1)
(2)
4
+
Speed
-OT
Homing direction
after reference Home
signal detection position LS
Home
position
Starting
direction for
homing
Homing speed [PA2_06]
Reverse
rotation +OT
Homing creep speed [PA2_07]
(2)
(1)
Home position shift unit
amount
[PA2_14]
(3)
(4)
Time
Servo-on [S-ON]
OFF
ON
Position control
OFF
ON
Homing [ORG]
OFF ON
+OT
ON
Home position LS [LS]
OFF
OFF
OFF
ON
ON OFF
ON
OFF
Controller,
sensor
Servo
amplifier
Encoder Z-phase
OFF ON OFF
Ready for servo-on
OFF
ON
OT detection
OFF
ON
OFF
+OT detection
OFF
Homing LS detection
Homing completion
ON
OFF
OFF
ON OFF
ON
OFF
OFF
ON
Servo
amplifier
Controller
Zero speed
In-position
[INP]
ON
OFF
ON
OFF
ON OFF
ON
ON
OFF
ON
OFF
ON OFF
ON
At the rotation direction selection point with zero speed, zero speed and in-position [INP] are
momentarily turned on. The signal change may fail to be sensed according to some scanning
periods of the host controller.
4-54 Automatic Operation Setting Parameter