CHAPTER 2 WIRING
CONT Through: Sequence Output Signal (Setting value 91 to 95)
This function allows communications input signals to be output via OUT signals of the hardware.
Function
The signals set to CONT 20 to 24 can be output through OUT signals 1 to 3 of the hardware. When
a CONT□ signal is allocated to an OUT signal, the ON/OFF status of the CONT signal is output
as a through signal to the OUT signal regardless of the function allocation of the corresponding
2
CONT signal.
CONT signals respectively correspond to CONT a to e
Corresponding CONT signals
CONTa
CONT20
CONTb
CONT21
CONTc
CONT22
CONTd
CONT23
CONTe
CONT24
Parameter setting
Set the values (91 to 95) corresponds to the parameter of output terminal function setting. The
setting values to the relevant signals are as follows.
PA3_51 to 53
No.
Name
Setting range
Change
51 OUT1 signal assignment 0 to 95 91 : CONTa through
92 : CONTb through
52 OUT2 signal assignment
93 : CONTc through
94 : CONTd through
53 OUT3 signal assignment
95 : CONTe through
Power
Description of I/O Signals 2-89