Absolute System
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA -A3
10
After all position data is updated in P0.050 - P0.052, P0.049 is automatically reset to 0. At
that point, the controller can access the values of P0.050 - P0.052.
P0.050 shows the status of the absolute encoder. When the status shows “absolute
position lost” or “overflow of number of revolutions”, it means the read absolute position is
invalid. In this case, you must re-establish the absolute origin position.
Start
Set P0.049 to 1 or 2
No
Set P0.049 to 0
Yes
Read
P0.050 - P0.052
End
10-22