Parameters
Note:
1. After finding the origin (sensor or Z), the servo has to decelerate to a stop. The stop position exceeds the origin by
a short distance:
If returning to the origin is not needed, set PATH to 0x00.
If returning to the origin is needed, set PATH to a 0x01 - 0x63 and set the route as PABS = 0.
Example:
When P6.000 = 0x0001, the servo automatically executes Path 1 after homing is complete.
Set the route of Path 1 (setting P6.002 & P6.003) as moving to the absolute position of 0.
2. If the origin is found (sensor or Z) and you want the servo to move an offset S and define the position after moving
as P, then set PATH = non-zero and set ORG_DEF = P - S, and this absolute Position command = P.
8
P6.001
Origin definition
Default: 0
Unit: -
Format: DEC
Settings:
Origin definition.
Address: 0602H
0603H
Control mode: PR
Setting range: -2147483648 to +2147483647
Data size: 32-bit
P6.002
PATH 1 definition
Default: 0x00000000
Unit: -
Format: HEX
Address: 0604H
0605H
Control mode: PR
Setting range: 0x00000000 - 0xFFFFFFFF
Data size: 32-bit
Settings:
Format of this parameter: (High word h) DCBA : (Low word L) UZYX
High word
Low word
DCB A
A
SPD, Target speedNote
B DLY, Delay time
C
AUTONote
D Reserved
UZ YX
X
TYPE, Path type
Y
OPT, Option
Z
ACC, Acceleration timeNote
U
DEC, Deceleration timeNote