Parameters
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
8
P5.095
Motion control macro command: command parameter #2
Address: 05BEH
05BFH
Default: 0
Control mode: All
Unit: -
Setting range: -2147483648 to +2147483647
Format: DEC
Data size: 32-bit
Settings:
Before issuing the macro command, set the relevant parameters in advance. The function of the
parameter is determined by the command code of the macro command. Not every macro command
requires this parameter.
P5.096
Motion control macro command: command parameter #1
Address: 05C0H
05C1H
Default: 0
Control mode: All
Unit: -
Setting range: -2147483648 to +2147483647
Format: DEC
Data size: 32-bit
Settings:
Before issuing the macro command, set the relevant parameters in advance. The function of the
parameter is determined by the command code of the macro command. Not every macro command
requires this parameter.
P5.097■
Motion control macro command: issue command / read Address: 05C2H
execution result
05C3H
Default: 0x0000
Control mode: All
Unit: -
Setting range: 0x0000 - 0x099F
Format: HEX
Data size: 16-bit
Settings:
Write to this parameter to issue a macro command; read this parameter to examine the execution result
of a macro command.
When you set the command code 0x0003 to this parameter, 0x1003 is returned if successful; and
0xF03X if unsuccessful (depending on the command description). If you issue a command that is not
supported, the error code 0xF001 is returned.