Parameters
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
8
P5.038■ Capture: number of capturing times
Address: 054CH
054DH
Default: 1
Unit: -
Format: DEC
Control mode: All
Setting
range:
1 to (value set by P5.010
value set by P5.036)
minus
Data size: 16-bit
Settings:
When Capture is not in operation, this parameter indicates the number of data sets expected to be
captured (readable and writable). When Capture is in operation, this parameter indicates the remaining
number of data sets to be captured (read-only). Each time one data is captured, the value of P5.038
decrements by 1 until the value is 0, indicating that capturing is complete.
Note: the total number of data sets from Compare, Capture, and E-Cam cannot exceed 800.
P5.039■ Capture: activate CAP control
Default: 0x2010
Unit: -
Format: HEX
Settings:
Address: 054EH
054FH
Control mode: All
Setting range: 0x0000 - 0xF13F
Data size: 16-bit
UZ YX
X Capture setting
Y Axis source of Capture
Z Trigger logic
U
Minimum interval between
each trigger
X: Capture setting
Bit
Function
Description
0
Activate Capture
Start capturing; after capturing is complete, set this bit to 0 automatically (Capture
disabled).
1
Reset position
After capturing the first data, reset the position of the first data. The position of the
reset point is set by P5.076.
2
Activate Compare
After capturing the first data, activate Compare, but this setting is invalid if Compare
is already activated.
3
Execute PR
Execute PR#50 automatically after capturing is complete.
Y: axis source of Capture
0: Capture is not working
1: CN5
2: CN1 (pulse command)
3: CN2
Note: when the source of Compare is the Capture axis, the source of Capture (P5.039.Y) cannot be changed.
Z: trigger logic
0: NO (normally open)
1: NC (normally closed)
8-172