ASDA-A3
8
P4.022
Analog speed input - offset compensation value
Address: 042CH
042DH
Default: 0
Control mode: S
Unit: mV
Setting range: -5000 to +5000
Format: DEC
Data size: 16-bit
Settings:
Manually adjust the compensation value for the offset.
P4.023
Analog torque input - offset compensation value
Address: 042EH
042FH
Default: 0
Control mode: T
Unit: mV
Setting range: -5000 to +5000
Format: DEC
Data size: 16-bit
Settings:
Manually adjust the compensation value for the offset.
P4.024
Level of undervoltage error
Default:
160
282
(220V
(400V
models)
models)
Unit: V (rms)
Format: DEC
Address: 0430H
0431H
Control mode: All
Setting range: 140 to 380
Data size: 16-bit
Settings:
When the voltage of the DC Bus is lower than P4.024 x 2 , the undervoltage alarm (AL003) occurs.
P4.025 -
P4.026
Reserved
P4.027
AL503 diagnosis time (220V models)
Default: 200
Unit: ms
Format: DEC
Control mode: All
Setting range: 1 to 500
Data size: 16-bit
Address: 0436H
0437H
Settings:
This parameter is used to adjust the time duration before the STO internal circuit diagnosis is performed
to avoid misdetection and triggering AL503.
P4.028 -
P4.043
Reserved
8-158