ASDA-A3
P3.005
Modbus communication
Default: 0x0000
Unit: -
Format: HEX
Settings:
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Parameters
Address: 030AH
030BH
Control mode: All
Setting range: 0x0000 - 0x0112
Data size: 16-bit
8
UZ YX
X Reserved
Y
Sets the servo drive as the master or
slave of Modbus
During Modbus communication, when the function
Z
code is 03H or 10H (read or write multiple words),
the system gives priority to read or write high-byte
data.
U Reserved
Y: sets the servo drive as the master or slave of Modbus.
0: slave of Modbus
1: master of Modbus
Z: during Modbus communication, when the function code is 03H or 10H (read or write multiple
words), the system gives priority to read or write high-byte data. Use this function for controllers
with different priority for transmitting high byte and low byte of the packets.
0: transmit low byte first
1: transmit high byte first
P3.006■ Digital input (DI) control switch
Default: 0x0000
Unit: -
Format: HEX
Address: 030CH
030DH
Control mode: All
Setting range: 0x0000 - 0x1FFF
Data size: 16-bit
Settings:
Control switch for the source of DI. Each bit of this parameter determines the input source of one DI
signal: Bit 0 - Bit 12 correspond to DI1 - DI13.
The setting for each bit is as follows:
0: DI status is controlled by the external terminal block.
1: DI status is controlled by P4.007.
For more information on DI functional planning, please see:
DI1 - DI8: P2.010 - P2.017
DI9 - DI13: P2.036 - P2.040