Parameters
P2.112Special bit register 4
Default: 0x2018
Unit: -
Format: HEX
Settings:
Address: 02E0H
02E1H
Control mode: All
Setting range: 0x0000 to 0x753F
Data size: 16-bit
Bit 7 6 5 4 3 2 1 0
Bit 15 14 13 12 11 10 9 8
8
Bit
Bit 0
Bit 1
Bit 2 - Bit 7
Bit 8
Bit 9
Bit 10
Bit 11, Bit 12
Bit 13
Bit 14
Bit 15
Function
Reserved
Enable AL089
Reserved
Motor hard stop function selection
Reserved
Enable AL040
Reserved
Regenerative brake method
Unit selection for internal Torque
command / internal torque limit
(P1.012 - P1.014)
Reserved
Description
-
0: disable AL089
1: enable AL089
-
Not applicable to Torque mode.
Motor hard stop 2 currently supports motors with
Hall sensors (PM.003.Y = 1) or absolute motors.
0: Motor hard stop 1
(Refer to the settings of P1.057, P1.058, and
P1.060.)
1: Motor hard stop 2
(Refer to the settings of P1.105, P1.106, and
P1.058.)
-
This function is supported only in Speed mode.
When the full-closed loop control is enabled
(P1.074 = 1), the system will force enable the
detection for AL040, so this function is invalid.
0: disable AL040
1: enable AL040
-
Use method 2 to release the capacitor voltage
faster which reduces the load voltage of the
capacitor.
0: method 1
1: method 2
0: 1%
1: 0.1%
-