ASDA-A3
After the full-closed loop function is enabled (P1.074.X = 1), restart and set the Capture function.
8
UZ YX
X Z phase source of full-closed loop homing
Z
Y Z phase source of semi-closed loop homing
U
X: Z phase source of full-closed loop homing
0: auxiliary encoder
1: motor
Reserved
Reserved
Y: Z phase source of semi-closed loop homing
0: motor
1: auxiliary encoder
Note: PR full-closed loop function is not yet supported.
P2.081
Pulse leakage detection function
Default: 1
Unit: -
Control mode: All
Setting range: 0 to 1
Address: 02A2H
02A3H
Format: DEC
Data size: 16-bit
Settings:
Pulse leakage detection function switch. Set 0 to disable this function; set 1 to enable this function.
This parameter is only applicable to pulse motors and when PM.003.U is set to 1 (main encoder
connects to CN5).
P2.082
Pulse leakage warning level
Default: 400
Unit: pulse
Format: DEC
Address: 02A4H
02A5H
Control mode: All
Setting range: 0 to 32767
Data size: 16-bit
Settings:
When P2.081 is set to 1 and the number of pulse leakage exceeds this set value, AL057 is triggered.
This parameter is only applicable to pulse motors and when PM.003.U is set to 1 (main encoder
connects to CN5).