Parameters
P1.106
Motor hard stop 2 - torque lower limit
Address: 01D4H
01D5H
Default: 0
Control mode: All
Unit: %
Setting range: -300 to +300
Format: DEC
Data size: 16-bit
Settings:
When Motor hard stop 2 is enabled (P2.112 [Bit 8] = 1), the settings of torque percentage (P1.057) and
level offset (P1.060) for Motor hard stop 1 are invalid. During motor operation, if the motor torque is
lower than this protection setting value and the duration of this condition exceeds the protection time
(P1.058), AL030 will be triggered.
8
P1.107 -
P1.110
Reserved
P1.111
Overspeed protection level
Default: Maximum motor speed x 1.1
Unit:
1
1
rpm (rotary)*
mm/s (linear)*
Format: DEC
Control mode: All
Address: 01DEH
01DFH
Setting range: 0 to 66000
Data size: 32-bit
Settings:
This function is to protect the motor from overspeeding, which can be applied to all control modes.
When the filtered motor speed exceeds this set speed, AL056 occurs.
Note: rotary means a permanent-magnet synchronous rotary motor; linear means a permanent-magnet synchronous
linear motor.
P1.112Single-direction torque limit
Address: 01E0H
01E1H
Default: 500
Control mode: All
Unit: %
Setting range: -500 to +500
Format: DEC
Data size: 16-bit
Settings:
Refer to the description of P4.044 for more details.
P1.113 -
P1.119
Reserved