Send Quote Requests to info@automatedpt.com
ASDA-A3
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Installation
400V models
Servo drive model
ASD-A3-0443-
ASD-A3-0743-
ASD-A3-1043-
ASD-A3-1543-
ASD-A3-2043-
ASD-A3-3043-
ASD-A3-4543-
ASD-A3-5543-
ASD-A3-7543-
ASD-A3-1B43-
ASD-A3-1F43-
Circuit breaker
10 A
15 A
15 A
20 A
25 A
30 A
50 A
50 A
60 A
90 A
90 A
Magnetic contactor (MC)
5 A
10 A
10 A
15 A
15 A
25 A
40 A
40 A
50 A
80 A
80 A
Fuse (Class T)
10 A
15 A
15 A
20 A
25 A
35 A
50 A
60 A
80 A
100 A
110 A
Note:
1. In the servo drive model name, represents the model type.
2. Operation mode: standard.
3. If the servo drive is equipped with a residual-current device (RCD) for electricity leakage protection,
select a circuit breaker with sensitivity of at least 200 mA and with minimum 0.1 sec working time to
avoid incorrect operation of the RCD.
4. Select the Type B residual-current device (RCD) with time delay, as the system ground wire may
contain DC electricity.
5. Use the fuse and circuit breaker that comply with the UL / CSA standard.
6. If authority in the country may designate I△n and maximum fault loop impedance, you shall follow the
rule in such a case.
Servo drive model
ASD-A3-0443-
ASD-A3-0743-
ASD-A3-1043-
ASD-A3-1543-
ASD-A3-2043-
ASD-A3-3043-
ASD-A3-4543-
ASD-A3-5543-
ASD-A3-7543-
ASD-A3-1B43-
ASD-A3-1F43-
Maximum fault loop impedance
TN system
TT system
1.6 Ω
220 Ω
1.3 Ω
220 Ω
1.3 Ω
220 Ω
1.01 Ω
220 Ω
0.85 Ω
220 Ω
0.75 Ω
220 Ω
0.69 Ω
220 Ω
0.65 Ω
220 Ω
0.65 Ω
220 Ω
0.62 Ω
220 Ω
0.62 Ω
220 Ω
2
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
2-19