Parameters
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
8
P1.054
Pulse range for position reached
Address: 016CH
016DH
Default: 167772
Control mode: PT / PR
Unit: pulse
Setting range: 0 to 16777216
Format: DEC
Data size: 32-bit
Settings:
In Position (PT) mode, when the pulse number error is smaller than the range set by P1.054, DO.TPOS
is on.
In Position Register (PR) mode, when the difference between the target position and the actual motor
position is smaller than the range set by P1.054, DO.TPOS is on.
Example:
For a rotary motor, if P1.054 = 167772 and the error is less than 167772 pulses, which equals 0.01
turns (167772 / 16777216 = 0.01), then DO.TPOS is on.
P1.055
Maximum speed limit
Rated speed of each model (rotary)*
Default: Automatically fills in after motor
parameter identification (linear)*
Unit:
1
1
rpm (rotary)*
mm/s (linear)*
Format: DEC
Address: 016EH
016FH
Control mode: All
Setting range: 0 to maximum speed
Data size: 16-bit
Settings:
Sets the maximum speed of the servo motor.
Note: rotary means a permanent-magnet synchronous rotary motor; linear means a permanent-magnet synchronous
linear motor.
P1.056
Motor output overload warning level
Default: 120
Unit: %
Format: DEC
Control mode: All
Setting range: 0 to 120
Data size: 16-bit
Address: 0170H
0171H
Settings:
When the value is 0 - 100 and the servo motor continuously outputs load that is higher than the setting
of P1.056, the pre-warning signal for overload (DO: 0x10, OLW) is on. If the value is over 100, the pre-
warning function is disabled.
8-72