ASDA-A3
8
7. Either signal 5 or signal 6 can be output, and this is determined by P1.048.X.
8. Position deviation: when event 7 occurs, if signal 4 (or 5) is off, it means the position has deviated
and AL380 can be triggered. Set whether to enable AL380 with P1.048.Y.
P1.049
Accumulated time to reach desired speed
Address: 0162H
0163H
Default: 0
Control mode: S / Sz
Unit: ms
Setting range: 0 to 65535
Format: DEC
Data size: 16-bit
Settings:
In Speed mode, when the absolute value of the difference between the Speed command and the motor
feedback speed is less than the range set in P1.047 and this status is kept for the time duration set in
P1.049, the digital output DO.SP_OK (DO: 0x19) is on. If the difference exceeds the range set in
P1.047, no matter how long it lasts, the system recalculates the duration.
P1.050 -
P1.051
Reserved
P1.052
Regenerative resistor value
Default:
Determined by the
the following table.
model.
Refer
to
Unit: Ohm
Address: 0168H
0169H
Control mode: All
Setting range: Refer to the following table.
Format: DEC
Data size: 16-bit
Settings:
220V
400V
Model
750 W or below
1 kW - 1.5 kW
2 kW - 3 kW
4.5 kW
5.5 kW - 7.5 kW
11 kW
15 kW
400 W
750 kW - 1 kW
1.5 kW - 2 kW
3 kW
4.5 kW - 5.5 kW
7.5 kW - 15 kW
Default (Ω)
100
100
20
20
20
20
20
80
80
80
80
80
80
Setting range (Ω)
60 - 750
30 - 750
15 - 750
10 - 750
8 - 750
6 - 750
5 - 750
80 - 750
60 - 750
40 - 750
30 - 750
25 - 750
15 - 750
Refer to the description of P1.053 for the parameter values when connecting the regenerative resistor
through different methods.
8-70