Parameters
P1.001● Input for control mode and control command
Address: 0102H
0103H
0x0000 (A3-M, A3-L)
Default: 0x000B (A3-F)
0x000C (A3-E)
Control mode: All
Unit: -
Setting range: 0x0000 - 0x112F
Format: HEX
Data size: 16-bit
Settings:
8
U Z YX
YX Control mode setting
- -
Z Direction control
U DIO value control
YX: control mode setting
Mode
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
Y = 1
PT
PR
S
T
Sz
Tz
▲
▲
▲
▲
▲
▲
Dual mode
▲
▲
▲
▲
▲
▲
▲
▲
▲
▲
Operates with the communication mode dedicated for 15MC series PLC models.
DMCNET mode
CANopen mode
EtherCAT mode
▲
▲
Multi-mode
▲
▲
▲
▲
▲
▲
Second development platform mode
PT: Position control mode; the command source is from the external pulse or the external analog
voltage (coming soon).
PR: Position control mode; the command source is from the 100 sets of internal registers which you
can select with DI.POS0 - DI.POS6. Multiple homing methods are also available.
S: Speed control mode; the command source is from the external analog voltage or the internal
register, which you can select with DI.SPD0 and DI.SPD1.
T: Torque control mode; the command source is from the external analog voltage or the internal
register, which you can select with DI.TCM0 and DI.TCM1.