ASDA-A3
8
P0.060
General range compare digital output 4 - lower limit
Address: 0078H
0079H
Default: 0
Control mode: All
Unit: -
Setting range: -2147483648 to +2147483647
Format: DEC
Data size: 32-bit
Settings:
Before using this function, set the digital output function to 0x2F (fourth set of general range
comparison) and the monitoring item of P0.020.
When the monitoring item value of P0.012 is within the range set in P0.060 and P0.061, and after the
filter time set by P0.053.U, this digital output is on.
P0.061
General range compare digital output 4 - upper limit
Address: 007AH
007BH
Default: 0
Control mode: All
Unit: -
Setting range: -2147483648 to +2147483647
Format: DEC
Data size: 32-bit
Settings:
Refer to the description of P0.060.
P0.062
Reserved
P0.063
Total duration of DC Bus voltage exceeding 400V or 800V
Address: 007EH
007FH
Default: 0
Control mode: All
Unit: ms
Setting range: 0 - 2147483647
Format: DEC
Data size: 32-bit
Settings:
220V models: records the total time during which the voltage of the DC Bus exceeded 400V.
400V models: records the total time during which the voltage of the DC Bus exceeded 800V.
P0.064 -
P0.078
Reserved
8-40