Control Mode
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
6
6.7.4.8 Set DI [0x0B] to switch between full- and semi-closed loop modes
DI [0x0B] is effective only when the full-closed loop function is enabled (P1.074.X = 1).
When the full-closed loop function is disabled, the setting of P1.072 is ignored.
Example 1 illustrates the semi-closed loop function in full-closed loop mode and Example 2
illustrates the semi-closed loop function which you usually use. The setting of P1.072 is effective
when the full-closed loop function is enabled, so pay special attention when using the semi-closed
loop functions.
Example 1: enable the full-closed loop function (P1.074.X = 1), set DI [0x0B] to On, E-Gear ratio
to 1 : 1, and P1.072 to 5000.
To have the motor run a cycle when the full-closed loop function is enabled,
the position command has to be 5000.
Example 2: disable the full-closed loop function (P1.074.X = 0), set DI [0x0B] to On, E-Gear ratio
to 1 : 1, and P1.072 to 5000.
To have the motor run a cycle when the full-closed loop function is disabled,
the position command has to be 16777216 because the DI setting is ineffective and
the setting of P1.072 is ignored.
Value: 0x0B
DI name
Description
FHS Switch between full- and semi-closed loop modes.
Note: PR full-closed loop function is not yet supported.
Triggering
method
Level
triggered
Control
mode
PT, PR*
6-56