Control Mode
6.7.4.5 Setting the low-pass filter time constant for full- / semi-closed loop
control
P1.075
Low-pass filter time constant for full- / semi-closed loop Address: 0196H
control
0197H
Default: 100
Control mode: PT / PR* (full-closed loop)
Unit: ms
Setting range: 0 - 1000
Format: DEC
Data size: 16-bit
Settings:
When the stiffness of the mechanical system between full- and semi-closed loops is insufficient, set the
proper time constant to enhance the stability of the system. In other words, create a semi-closed loop
effect in the transient state. After the system reaches a steady state, the full-closed loop effect is
created. When the stiffness is sufficient, set to bypass. Set the value to 0 to disable the low-pass filter
function (bypass).
If the stiffness of the mechanical system is high, decrease the value of P1.075 or set the value to 0 to
disable the low-pass filter function. If the stiffness of the mechanical system is low, increase the value
of P1.075.
Note: PR full-closed loop function is not yet supported.