2. Calculating the actual value
Calculating theoretical values is infeasible if the system does not use screws for
transmission or the system consists of complex mechanical parts. In this case, use the JOG
function to operate the motor in a single direction at low speed when the full-closed loop
function is disabled, and then calculate the value of P1.072 by using the Feedback position
[PUU] and Auxiliary encoder feedback [Pulse] observed with the Scope function of
ASDA-Soft.
Step 1: disable the full-closed loop function by setting P1.074.X to 0.
Step 2: open the Scope function, select Feedback position [PUU] for CH1 and Auxiliary
encoder feedback [Pulse] for CH2, and then click Start to start the scope.
CH1 32 bit
[IDX] Normal
Feedback position
[PUU]
CH2 32 bit
[IDX] Normal
Auxiliary encoder
feedback [Pulse]