Test Operation and Panel Display
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
4
4.5.5 Trial run without load (Position mode)
Before starting the trial run without load, firmly secure the motor base to avoid any danger
caused by the force generated by the motor during speed changes.
Step 1: set the control mode of the servo drive to Position mode. Set P1.001 to 1 for Position
mode. Then cycle the power to the servo drive.
Step 2: in Position mode, set the digital input settings for the trial run as shown in the following
table.
Digital input
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
DI13
Parameter setting
value
P2.010 = 101
P2.011 = 108
P2.012 = 111
P2.013 = 112
P2.014 = 102
P2.015 = 0
P2.016 = 0
P2.017 = 0
P2.036 = 0
P2.037 = 0
P2.038 = 0
P2.039 = 0
P2.040 = 0
Symbol
SON
CTRG
POS0
POS1
ARST
-
-
-
-
-
-
-
-
Function description
Servo activated
Command triggered
Position selection
Position selection
Alarm reset
DI disabled
DI disabled
DI disabled
DI disabled
DI disabled
DI disabled
DI disabled
DI disabled
CN1 Pin No.
DI1- = 9
DI2- = 10
DI3- = 34
DI4- = 8
DI5- = 33
-
-
-
-
-
-
-
-
You can program the digital inputs of Delta’s servo drive by referring to Section 8.1 Digital input
(DI) descriptions.
The default setting includes the negative limit, positive limit, and emergency stop functions;
therefore, if any alarm occurs after you complete the settings, cycle the power to the servo drive
or set DI5 to on to clear the alarm. Please refer to Section 4.5.
4-24