Test Operation and Panel Display
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
4
4.5.3 JOG trial run without load
It is easy to test the motor and servo drive using a JOG trial run without load since no extra wiring
is needed. For safety reasons, it is recommended that you set JOG at low speed. Follow these
steps.
Note: the JOG trial run is not supported when P1.001.X = B or C or P1.001.Y = 1.
Step 1: JOG trial run is available only when the servo drive is in the Servo On state. The drive
can be forced into the Servo On state by setting P2.030 to 1 or by the controller.
Step 2: set the JOG speed (unit: rpm) with P4.005. Press the S key to display the JOG speed.
The default is 20 rpm.
Step 3: press the ▲ or ▼ key to adjust the JOG speed. In the following example, the speed is
set to 100 rpm.
Step 4: press the S key to display “JOG” and enter JOG mode.
Step 5: after completing the trial run, press the M key to exit JOG mode.
S
Display JOG speed.
Its default value is 20 rpm.
Press the keys to adjust
the JOG speed.
4-20
S
JOG mode
Adjust the speed to 100 rpm.
Display "JOG" and enter JOG mode.
After entering JOG mode, make the
motor run in a counterclockwise or
clockwise direction by pressing the
or key. Release the key to stop
the operation.
P (CCW)
N (CW)
M Press the M key to
exit JOG mode.
Exit