4.5 Testing
This section is divided into two parts. The first part introduces testing without load and the
second part describes testing when the servo motor is running with load. To avoid danger,
operate the servo motor without load first.
4.5.1 Testing without load
Remove the load from the servo motor, including coupling on the shaft and accessories, to
avoid any damage to the servo drive or machine. This prevents the parts on the motor shaft
from falling off and possibly causing personnel injury or equipment damage during operation.
Run the motor without load first to see if the servo motor can run during normal operation.
Caution: to prevent danger, it is strongly recommended that you check if the motor can operate
normally without load first. Then, try operating the motor with load.
Check the following items carefully before operation.
Inspection before
operation
(without power)
Inspection during
operation
(power is applied)
◼ Check for any obvious visible damage.
◼ The wires at the wiring terminal should be isolated.
◼ Make sure the wiring is correct to avoid damage or any abnormal
operation.
◼ Check for and remove any electrically conductive objects, including sheet
metal and screws, or inflammable objects inside or near the servo drive.
◼ Check if the control switch is in the Off state.
◼ Do not place the servo drive or external regenerative resistor on
inflammable objects.
◼ To ensure the electromagnetic brake works, check if the stop and circuit
breaker functions are working normally.
◼ Reduce the electromagnetic interference if there is electromagnetic
interference with the peripheral devices.
◼ Make sure the external voltage level of the servo drive is correct.
◼ Protect the encoder cable from excessive stress. When the motor is
running, make sure the cable is not worn or stretched.
◼ Contact Delta if the servo motor vibrates or makes unusual noise during
operation.
◼ Make sure the settings for the parameters are correct. Different machinery
has different characteristics. Adjust the parameters according to the
characteristics of each machine.
◼ Reset the parameters when the servo drive is in the Servo Off state, or it
may cause malfunction.
◼ If there is no contact noise or other abnormal noise when the relay is
operating, please contact Delta.
◼ Check if the power indicator and LED display work properly.
◼ The 7.5 kW model is controlled by PWM. When the temperature is lower
than 40°C (104°F), the fan stops running.