Test Operation and Panel Display
4.4.3 Digital input diagnosis operation
You can switch to the Diagnosis mode by the following steps. When DI1 - DI10 are triggered by
the external signal, the panel shows the corresponding signal in bit. When it shows 1, it means
the DI is on.
For example, if it shows 1FE1, E is in hexadecimal format; it will be 1110 when it transfers to
binary format. Then, DI6 - DI8 are on.
4
S
The panel displays in
hexadecimal format.
1 1111 1110 0001
13 12 11 10 9 8 7 6 5 4 3 2 1
Binary code
Corresponding
DI
4.4.4 Digital output diagnosis operation
You can switch to the Diagnosis mode by the following steps. When DO1 - DO5 are triggered by
the output signal, the panel shows the corresponding signal in bit. When it shows 1, it means the
DO is on.
For example, if it shows 1F, F is in hexadecimal format; it will be 1111 when it transfers to binary
format. Then, DO1 - DO4 are on.
S
The panel displays in
hexadecimal format
0001 1111
5 4321
Binary code
Corresponding
DO