3.10.7 Validation test
When installing, maintaining, or changing the servo drive, ensure to perform the following
validation tests. (It is suggested that you keep a record of the test results.)
With EDM diagnosis (SIL3 system)
(1) When either SF1 or SF2 signal is off, the servo motor cannot be operated.
(2) When you switch the SF1 and SF2 signals to ON or OFF, the input / output logic has to
be in accordance with the following table.
Signal
STO
SF1+
SF1-
SF2+
SF2-
Diagnostic output
(EDM)
ON
ON
OFF
Status of opto-isolator
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
Without EDM diagnosis (SIL2 system)
(1) When either SF1 or SF2 signal is off, the servo motor cannot be operated.
(2) When SF1 and SF2 signals are both ON or OFF, neither AL501 nor AL502 is triggered.
Note:
1. Ensure to perform the validation tests once every 3 months even if you do not install, maintain, or
change the servo drive.
2. If an error or danger is diagnosed, switch the safety input signals to OFF to have the servo drive enter
the safe state.
3-132