Wiring
(4) When P1.120 = 1 and the Servo On / Off command is sent through EtherCAT / CANopen
communication
SF1
SF2
OFF
ON
OD 6040h
0xF
0x6
0x7
0xF
3
DO.SRDY(0x01)
OFF
ON
DI.ARST
OFF
ON
OFF
Motor current
OFF
ON
EDM
ON
OD 6041h status
Panel display
Fault
AL500
OFF
Switch on disabled
N-RDY
Ready to
switch on
Operation
Switched on enabled
Content before alarm occurs
(5) When P1.120 = 2 and the Servo On / Off command is sent with external DI
SF1
SF2
OF F
ON
DI.SON(0x01)
ON
DO.SRDY(0x01)
OF F
ON
Motor current
OF F
ON
EDM
ON
OF F
Panel display
-STO-
Content before alarm occurs
Note: if you switch the STO signals to ON when the servo drive sends the position or speed command to
the motor, it may cause drastic motor rotation. Before switching the STO signals to ON, check if
there is any command input and ensure personnel safety.