(2) AL501(SF1 lost) / AL502 (SF2 lost) (signal loss or signal error)
When either SF1 signal or SF2 signal becomes OFF, the STO function is activated, the
circuit cuts off the current to the motor within 10 ms, and the servo drive is Off, triggering
AL500. After 1 second, AL501 or AL502 is triggered. The following diagram illustrates how
AL501 is triggered.
The panel displays either βAL500β or β-STO-β according to the setting of P1.120.
SF1
ON
OF F
SF2
Motor current
ON
Max.10 ms
ON
OF F
EDM
OF F
DO.SRDY(0x01)
ON
Alarm
No alarm
Max.10 ms
OF F
1 s
AL500
AL501
Note: when SF1 becomes OFF, AL501 occurs. When SF2 becomes OFF, AL502 occurs.