Wiring
3.10.5.2 Alarm triggering
(1) AL500 (STO function is activated)
When either SF1 signal or SF2 signal becomes OFF, the STO function is activated, the
circuit cuts off the current to the motor within 10 ms, and the servo drive is Off, triggering
AL500.
When both SF1 and SF2 signals become OFF, the servo drive still displays AL500. Refer to
the following diagram.
The panel displays either β€œAL500” or β€œ-STO-” according to the setting of P1.120.
3
SF1
SF2
Motor current
EDM
ON
ON
ON
OF F
DO.SRDY(0x01)
ON
Alarm
No alarm
OF F
OF F
Max.10 ms
OF F
10 ms
10 ms
ON
OF F
AL500