ASDA -A3
3
3.2.6 Wire selection
3.2.6.1 Wire diameters and terminals / ferrules
The recommended wire for connectors and signal wiring for the servo drive as listed in the
following tables:
For the pluggable terminal blocks on 1.5 kW (or below), use wire ferrules (end cord
insulated terminals).
For the screw terminal blocks on 2 kW (or above) models, use ring terminals.
The suggested brand in the following table is K.S. Terminals Inc. Refer to Section 3.1.6.2
and 3.2.6.2 for the suitable ferrule / terminal specifications.
Servo drive model
ASD-A3-0443- 2
DC24V, DC0V
Wire
diameter
Wire
ferrule
E0308
ASD-A3-0743- 2
ASD-A3-1043- 2
0.32 mm2
(22 AWG)
E0308
E0308
ASD-A3-1543- 2
E0308
R, S, T, P1, P2
Wire
diameter
0.32 mm2
(22 AWG)
Wire
ferrule
E0308
0.52 mm2
(20 AWG)
E0512
E0512
0.82 mm2
(18 AWG)
E1012
U, V, W
Wire
diameter
Wire
ferrule
0.82 mm2
(18 AWG)
E1012
E1012
1.3 mm2
(16 AWG)
E1512
E1512
P3, D, C, ㊀
Wire
diameter
0.32 mm2
(22 AWG)
Wire
ferrule
E0308
0.52 mm2
(20 AWG)
E0512
E0512
0.82 mm2
(18 AWG)
E1012
Servo drive model
ASD-A3-2043- 2
DC24V, DC0V
Wire
diameter
Ring
terminal
RVBL1-4
ASD-A3-3043- 2
ASD-A3-4543- 2
ASD-A3-5543- 2
ASD-A3-7543- 2
ASD-A3-1B43- 2
ASD-A3-1F43- 2
0.52 mm2
(20 AWG)
0.82 mm2
(18 AWG)
RVBL1-4
RVBL1-4
RVBL1-4
RVBL1-4
RVB1-5
RVB1-5
R, S, T, P1, P2
Wire
diameter
1.3 mm2
(16 AWG)
2.1 mm2
(14 AWG)
3.3 mm2
(12 AWG)
Ring
terminal
RVBL2-4
RVBL2-4
RVBS5-4
5.3 mm2
(10 AWG)
RVBS5-4
RVBS5-4
8.4 mm2
(8 AWG)
RNYBS8-5
RNYBS8-5
U, V, W
Wire
diameter
Ring
terminal
2.1 mm2
(14 AWG)
RVBL2-4
RVBL2-4
3.3 mm2
(12 AWG)
RVBS5-4
RVBS5-4
5.3 mm2
(10 AWG)
8.4 mm2
(8 AWG)
RVBS5-4
RVB5-6
RNYBS8-6
P3, C, ㊀
Wire
diameter
Ring
terminal
1.3 mm2
(16 AWG)
RVBL2-4
RVBL2-4
2.1 mm2
(14 AWG)
3.3 mm2
(12 AWG)
5.3 mm2
(10 AWG)
8.4 mm2
(8 AWG)
RVBL2-4
RVBS5-4
RVBS5-4
RVBS5-4
RNYBS8-5
Note:
1. In the servo drive model name, 2 represents the model type.
2. The shield should connect to the
phase of the ground terminal.
3. When wiring, use the wires suggested in this section to avoid danger.
4. Choose the suitable terminals that comply with the wiring specifications. Use a crimping tool to
properly crimp the terminals / ferrules and wires.
5. Do not use bare wires for wiring, or the loose wires may cause accidents.
6. For wiring with wire ferrules, refer to Section 3.1.6.2.