AL510 Internal parameter update program of the servo drive is abnormal
Trigger condition
and cause
Internal parameter update program of the servo drive is abnormal.
Checking method
and corrective action
If this alarm occurs when the motor parameter identification function is executing,
cycle power on the servo drive and re-execute the motor parameter identification
function.
How to clear the
alarm?
N/A
AL520 Calculation program timeout
Trigger condition
and cause
Servo drive calculation program timeout.
1. Cycle power on the servo drive.
Checking method
and corrective action
2.
If the alarm persists, disable the vibration elimination function by setting [Bit 8]
and [Bit 9] of P2.094 to 0.
How to clear the
alarm?
N/A
AL521 Vibration elimination parameter error
Condition: the input value for the vibration elimination parameter is not appropriate.
Trigger condition
and cause
Cause:
1. Your input value for the vibration elimination parameter is not appropriate.
2. The Bode plot is in error due to other factors when the System Analysis tool
is in operation.
Checking method Perform system analysis again and correctly set the value for the vibration
and corrective action elimination parameter.
How to clear the
alarm?
1. Perform system analysis again and correctly set the value for the vibration
elimination parameter.
2. If the issue persists, disable the vibration elimination function by setting [Bit 8]
and [Bit 9] of P2.094 to 0.
.
AL555 System failure
Trigger condition
and cause
Servo drive DSP is in error.
Checking method If this alarm occurs, send your servo drive directly back to Delta without making
and corrective action any modification.
How to clear the
alarm?
N/A