Troubleshooting
AL3E2 Communication synchronization signal is sent too soon
Trigger condition
and cause
Condition: the synchronization signal is received too early.
Cause: the communication synchronization signal is sent too soon.
1. Make sure the setting of communication cycle period (OD 1006h) is identical
to that of the controller.
Checking method 2. Modify the synchronization error range setting (P3.009.U). (For A3-M and
and corrective action
A3-F models.)
3. Ensure the correct time sequence of sending packets from the controller.
A drift or delay in packet sending time causes synchronization failure.
How to clear the
alarm?
NMT: reset node or OD 6040h [Bit 7] (Fault reset).
14
AL3E3 Communication synchronization signal timeout
Trigger condition The target command is not received within a continuous communication cycle in IP
and cause
mode (except the CANopen B mode).
1. Make sure the communication between the servo drive and controller is good.
2. Make sure the setting of communication cycle period (OD 1006h) is identical
to that of the controller.
Checking method 3. Modify the synchronization error range setting (P3.009.U). (For A3-M and
and corrective action
A3-F models.)
4. Modify the setting of IP command timeout (P3.022.YX). (For A3-E models.)
5. Ensure the correct time sequence of sending packets from the controller.
A drift or delay in packet sending time causes synchronization failure.
How to clear the
alarm?
NMT: reset node or OD 6040h [Bit 7] (fault reset).
AL3F1 Absolute position command of the communication type servo drive is in error
Trigger condition
and cause
Condition: when the bus communication type (CANopen, DMCNET, and
EtherCAT) servo drive is in combination with an incremental motor and the position
overflow occurs with the absolute origin position not established, the absolute
positioning command is issued.
Cause:
1. The absolute origin position is not established.
2. Overflow occurs since the motor keeps rotating in the same direction.
Checking method
and corrective action
Establish the absolute origin position.
How to clear the
alarm?
Establish the absolute origin position.