Troubleshooting
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
14
AL285 Software negative limit
Trigger condition
and cause
Condition: the feedback position exceeds the software negative limit.
Cause: the software negative limit is triggered.
Checking method
and corrective action
Software negative limit triggering is determined by the feedback position. Set an
appropriate deceleration time to achieve the desired effect. For more information,
refer to the description of P5.003.
How to clear the
alarm?
The alarm is automatically cleared after the motor moves away from the limit.
AL289 Position counter overflows
Trigger condition
and cause
Position counter overflows.
1. Set the gear ratio according to the actual application requirements and the
total traveling distance of the absolute motor to avoid overflow of the feedback
Checking method
counter.
and corrective action 2. If P2.069.Z is set to 1 (enabling the function of preventing the rotary axis
position from being lost when overflow occurs), set P2.070 [Bit 2] to 1 (no
overflow warning).
How to clear the
alarm?
DI.ARST
AL301 CANopen synchronization failure
Trigger condition
and cause
Condition: the synchronization with the controller fails when you use the CANopen
IP mode (B mode).
Cause: communication fails to synchronize.
1. Make sure the communication between the servo drive and controller is good.
Checking method 2. After eliminating any problems that you find, allow the controller to re-send the
and corrective action
synchronization signal and ensure that it is sent successfully.
How to clear the
alarm?
3. Modify the setting for P3.009 (the default value is suggested).
NMT: reset node or OD 6040h [Bit 7] (Fault reset).
AL302 Synchronization signal of CANopen is sent too soon
Trigger condition
and cause
Condition: the synchronization signal is received too early when you use the
CANopen IP mode (B mode).
Cause: the synchronization signal of CANopen is sent too soon.
1. Make sure the setting of communication cycle period (OD 1006h) is identical
Checking method
to that of the controller.
and corrective action 2. Modify the synchronization error range setting (P3.009.U). (For A3-M and
A3-F models.)
14-64