Troubleshooting
AL25F Second development platform - an error occurred when the object dictionary is
accessed
Condition: when an object dictionary command is used, an error occurred because
Trigger condition
and cause
the value is out of range or the object dictionary does not exist.
Cause: when the object dictionary is accessed, the value of the object dictionary is
out of range or the firmware does not support the object dictionary.
Checking method
and corrective action
Check if the setting for this object dictionary in the program is correct.
If you took the corrective action but the issue persists, contact the local distributor
or technician.
How to clear the
alarm?
DI.ARST
14
AL261 Second development platform - commands dedicated for the master cannot be used
when the master mode is not enabled
Trigger condition
and cause
Condition: when the servo drive is in Modbus slave mode (P3.005.Y = 0),
a command dedicated for the master is used.
Cause: master mode is not enabled.
Checking method
and corrective action
Refer to the command descriptions for the second development platform to ensure
the correct use of the commands. If you took the corrective action but the issue
persists, contact the local distributor or technician.
How to clear the
alarm?
DI.ARST
AL262 Second development platform - read / write address in the master mode is out of
range
Trigger condition When you use the read / write command in the master mode, the specified
and cause
address is out of range.
Checking method
and corrective action
Refer to the command descriptions for the second development platform to ensure
the correct use of the commands. If you took the corrective action but the issue
persists, contact the local distributor or technician.
How to clear the
alarm?
DI.ARST
AL283 Software positive limit
Trigger condition
and cause
Condition: the feedback position exceeds the software positive limit.
Cause: the software positive limit is triggered.
Checking method
and corrective action
Software positive limit triggering is determined by the feedback position. Set an
appropriate deceleration time to achieve the desired effect. For more information,
refer to the description of P5.003.
How to clear the
alarm?
The alarm is automatically cleared after the motor moves away from the limit.