Troubleshooting
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
AL21B Second development platform - memory stack is out of range
How to clear the
alarm?
DI.ARST
14
AL21D Second development platform - a divisor in an expression is zero in the program
Trigger condition
and cause
Condition: a divisor in an expression is zero in the program.
Cause: programming error of the second development platform.
Checking method
and corrective action
Check if the programs of the second development platform contain expressions
with zero as the divisor. If you took the corrective action but the issue persists,
contact the local distributor or technician.
How to clear the
alarm?
DI.ARST
AL221 Second development platform - a non-existing mode is used
Trigger condition
and cause
Condition: the MODE command is used to execute a non-existing mode number.
Cause: incorrect use of the command of the second development platform.
Checking method
and corrective action
Refer to the command descriptions for the second development platform to ensure
the correct use of the commands. If you took the corrective action but the issue
persists, contact the local distributor or technician.
How to clear the
alarm?
DI.ARST
AL223 Second development platform - some commands are not allowed to be used when the
servo is in the ERROR or FAULT state
Trigger condition
and cause
Condition: the servo is in the ERROR or FAULT state when a specific command is
used.
Cause: incorrect use of the command of the second development platform.
Refer to the command descriptions for the second development platform to ensure
Checking method if the servo can be in the ERROR or FAULT state when the command is used.
and corrective action If you took the corrective action but the issue persists, contact the local distributor
or technician.
How to clear the
alarm?
DI.ARST
AL22D Absolute positioning cannot be executed when E-Cam is engaged
Trigger condition
and cause
Condition: absolute positioning is executed when E-Cam is engaged.
Cause: absolute positioning is executed when E-Cam is engaged.
Checking method
and corrective action
Check if E-Cam is engaged when the servo is executing absolute positioning.
How to clear the
alarm?
DI.ARST
14-58