Troubleshooting
AL127 PDO object is write-protected when servo drive is on
Trigger condition
and cause
PDO object is write-protected (unchangeable) when the servo drive is on.
Checking method Make sure no specified object is written when the servo drive receives or sends
and corrective action the PDO in the Servo On state.
How to clear the
alarm?
NMT: reset node, OD 6040h [Bit 7] (Fault reset), or DI.ARST.
14
AL128 Error occurs when PDO object is read from EEPROM
Trigger condition An error occurs when the default value is loaded from ROM at start-up.
and cause
All objects are automatically restored to default values.
Checking method Check if an error occurs because the specified object is read from EEPROM when
and corrective action the servo drive receives or sends the PDO.
How to clear the
alarm?
NMT: reset node, OD 6040h [Bit 7] (Fault reset), or DI.ARST.
AL129 Error occurs when PDO object is written to EEPROM
Trigger condition
and cause
An error occurs when the PDO object is written to EEPROM.
Checking method Check if an error occurs because the specified object is written to EEPROM when
and corrective action the servo drive receives or sends the PDO.
How to clear the
alarm?
NMT: reset node, OD 6040h [Bit 7] (Fault reset), or DI.ARST.
AL130 Accessing address of EEPROM is out of range
Trigger condition
and cause
The amount of data in the ROM is greater than the allowable space specified by
the firmware. It is probably because the firmware has been updated, but the data
in the ROM was stored by the previous firmware version.
Checking method Check if the specified object causes the accessing address in EEPROM exceeds
and corrective action the range when the servo drive receives or sends the PDO.
How to clear the
alarm?
NMT: reset node, OD 6040h [Bit 7] (Fault reset), or DI.ARST.
AL131 EEPROM CRC calculation error
Trigger condition The data in ROM is damaged. All objects are automatically restored to default
and cause
values.
Checking method
and corrective action
Check if the specified object causes a CRC calculation error in EEPROM when the
servo drive receives or sends the PDO. Usually, this alarm is caused by an error in
DSP.
How to clear the
alarm?
NMT: reset node, OD 6040h [Bit 7] (Fault reset), or DI.ARST.