Troubleshooting
AL086 Regenerative resistor overload
Condition: excessive energy in the capacitor of the servo drive is released to the
regenerative resistor causing overload of the resistor.
Cause:
Trigger condition
and cause
1. Incorrect selection of the regenerative resistor or no connection to an external
regenerative resistor.
2. Incorrect parameter settings for P1.052 and P1.053.
3. Other energy (such as interference) is input to the servo drive or the input
voltage is higher than the allowable rated voltage.
4. Malfunction of the servo drive hardware.
1. Check the connection for the regenerative resistor and correctly set the values
of P1.052 and P1.053.
2. Reassess whether the regenerative energy exceeds the value of P1.053.
If so, replace the regenerative resistor with a regenerative resistor that has a
higher capacity.
3. Use a voltmeter to measure if the input voltage from the power supply is within
the allowable rated voltage (refer to Appendix A Specifications). If the input
Checking method
voltage exceeds the rated range, remove the interference source.
and corrective action 4. Measure the voltage between P3 and terminals. If it does not match the
displayed DC Bus voltage when you enter the monitoring code 14 to P0.002,
the servo drive may be malfunctioning. Send your servo drive back to the
distributor or contact Delta.
5. If you took the preceding actions and the issue persists, use a scope with a
differential probe to measure whether the input voltage has high-frequency
signal interference. If there is interference, remove the interference source,
How to clear the
alarm?
and use the right voltage source or connect the regulator in series.
DI.ARST
14
AL087 Hardware device error
Trigger condition
and cause
Hardware device is in error.
Checking method Send your servo drive back to the distributor or contact Delta.
and corrective action
How to clear the
alarm?
N/A
AL088 Servo function operational alarm
Trigger condition
and cause
Condition: too many motor control functions on the servo drive are enabled.
Cause: servo function operational alarm.