Troubleshooting
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ASDA-A3
14
AL058 Excessive position deviation after initial magnetic field detection is complete
Condition:
Trigger condition
and cause
1. After the initial magnetic field detection is complete, the servo system then
attempts, but fails to reduce the existing position error.
2. If the controller issues commands when the servo system is not fully settled,
the position error might thus be greater and cannot be reduced.
Cause: the controller issues commands during initial magnetic field detection.
1. Check if the controller has issued a command immediately when it is powered
on. Use the software scope and select “Command Position [PUU]” as the
input signal for the channel to monitor whether there is a command issued. If
Checking method
and corrective
action
so, increase the delay time for the controller to issue the command after it is
powered on.
2. If the controller time sequence cannot be modified due to surge interference or
other factors when the power is on, set P2.088 [Bit 4] to 1 to prohibit the servo
from receiving controller commands during the initial magnetic field detection.
How to clear the
alarm?
DI.ARST
AL05B Motor type setting does not match
Condition: incorrect setting of PM.000.
Cause:
Trigger condition
and cause
1. A Delta motor is connected to CN2 as the main encoder, but PM.000 is not set
to 0.
2. A Delta motor with magnetic encoder is used, but PM.000 or PM.003 is set
incorrectly.
1. Check the setting of PM.000.
Checking method 2. Make sure the type of motor used complies with the setting of PM.000.
and corrective action 3. If a Delta motor with magnetic encoder is used, set PM.000 to 0 and PM.003
to 0x1XX2.
How to clear the
alarm?
Cycle power on the servo drive.
14-34