Troubleshooting
AL02B Motor data error
Trigger condition
and cause
Accessing the internal data of the motor is in error.
Checking method
and corrective action
Send your servo motor back to Delta.
How to clear the
alarm?
N/A
AL02C Servo drive overload
Condition: servo drive is overloaded.
Cause:
Trigger condition
and cause
1. The load is over the rated range and the servo drive is in a continuous
overload condition.
2. Improper setting for the gain parameters or the motion profile of the control
system.
3. Motor wiring error.
4. The encoder is damaged or malfunctioning.
Checking method
and corrective
action
How to clear the
alarm?
1. Set P0.002 = 55 to monitor the current feedback. Check if the motor current
exceeds the rated output current of the servo drive for a long period of time.
2. (a) Check if there is any mechanical vibration. If so, properly adjust the gain
parameters.
(b) Set a higher acceleration / deceleration time constant or a lower target
speed.
3. Check if the wiring of the motor power cable and encoder cable is correct.
4. Replace the encoder.
DI.ARST
14
AL02F Blocked rotor protection
Condition: the servo drive is overloaded, and the motor speed keeps at 10 rpm (or
below) or the rotor is blocked.
Trigger condition
and cause
Cause:
1. The motor or the connected mechanical part is locked, causing the motor not
to rotate.
2. The motor is running at an extremely low speed or the rotor is blocked for a
long time.