Troubleshooting
AL020 Serial communication timeout
Condition: RS-485 communication error.
Trigger condition
and cause
Cause:
1. Improper setting for P3.004 (Modbus communication timeout).
2. Servo drive has not received the communication command for a long time and
has timed out (refer to P3.004).
1. Check and correctly set the value for the communication timeout parameter.
Checking method
and corrective action
2.
Check if the communication cable is loose or disconnected and make sure it is
correctly wired.
How to clear the
alarm?
DI.ARST
14
AL022 RST power error
Trigger condition
and cause
Condition: RST power cable is loose or there is no power. The error type of AL022
is a warning by default. To set AL022 as an alarm, you can set P2.066 [Bit 12] to 1.
Cause: RST power error.
Check if the RST power cable is loose or there is no power. For 1.5 kW (or below)
ASDA-A3 servo drives, this alarm occurs when all three phases are not connected
Checking method to the power supply. For 2 kW (or above) ASDA-A3 servo drives, this alarm occurs
and corrective action when one single phase is not connected to the power supply. Correctly connect the
power to the servo drive. If the issue persists, send your servo drive back to the
distributor or contact Delta.
How to clear the
alarm?
DI.ARST
AL023 Early overload warning
Trigger condition
and cause
Early overload warning.
1. Check if the motor is overloaded and refer to the corrective actions for AL006
for troubleshooting.
Checking method
and corrective action 2. Check if the value of P1.056 (Motor output overload warning level) is set too
low. If so, set the value higher, or set the value greater than 100 to disable the
warning function.
How to clear the
alarm?
DI.ARST