ASDA-A3
14
AL012 Calibration error
Trigger condition
and cause
Condition: the calibration value exceeds the allowable value during electrical
calibration.
Cause:
1. The analog input contact is not correctly returned to zero.
2. The detection device is damaged.
1. Check if the voltage level at the analog input contact is the same as the
Checking method
ground potential.
and corrective action 2. Cycle power and execute the calibration again. If the issue persists after
power cycling, send your servo drive back to the distributor or contact Delta.
How to clear the
alarm?
Remove the connection cable for CN1 and then execute auto calibration.
AL013 Emergency stop
Trigger condition
and cause
The emergency stop button is pressed.
Checking method
and corrective action
Make sure the emergency stop button is off.
How to clear the
alarm?
Set DI.EMGS to off to clear the alarm.
AL014 Negative limit error
Condition: negative limit switch is triggered.
Trigger condition
and cause
Cause:
1. Negative limit switch is triggered.
2. Servo system is unstable.
Checking method 1. Make sure the negative limit switch is off.
and corrective action 2. Check the parameter setting or re-estimate the motor capacity.
How to clear the
alarm?
The alarm is automatically cleared after the motor moves away from the limit.
AL015 Positive limit error
Condition: positive limit switch is triggered.
Trigger condition
and cause
Cause:
1. Positive limit switch is triggered.
2. Servo system is unstable.
Checking method 1. Make sure the positive limit switch is off.
and corrective action 2. Check the parameter setting or re-estimate the motor capacity.
How to clear the
alarm?
The alarm is automatically cleared after the motor moves away from the limit.
14-16